Feature Historian CopperCube
Type of Product Software. User installed Windows application. User supplies host computer and host Database. Stand-alone hardware appliance
Mounting Options IT based (requires a Windows computer or Virtual Machine). Typically, one instance, located in a central IT location. Flexible. Typically one per building. Either installed alongside controllers (and powered with 24 VAC) or in any location with standard wall outlet (and powered with 120/240 VAC).
Archiving Capacity Up to a maximum of 10,000 TLs Up to a maximum of 5000 TLs
Types of data collected BACnet Trend logs, BACnet Events, BACnet Access Control Events BACnet Trend logs.
[Sent to Kaizen, but not stored] BACnet Objects, BACnet Events and BACnet Controller Database backups.
User Interface None. Use enteliWEB or ORCAview Primary: built-in web-based GUI (configuration).
Secondary: Coppertree Kaizen and enteliWEB
Methods to view Trend log data enteliWEB and ORCAview Coppertree Kaizen, enteliWEB, CopperCube GUI
Methods to access raw Trend log data Pull data: via ODBC, direct SQL Queries, and BACnet ReadRange services Pull data: via API (CSV, JSON formats).
Push data: via send to CopperTree Kaizen Vault, and send to external SQL server
Backup and Restore Capability Relies on host database system (MySQL, MS SQL, Backup) and/or Windows backup utilities. Built in backup and restore solution to external USB disk.
Multi-site capable No. Single BACnet network or WAN required. Yes. Supports simultaneous data collection from multiple BACnet networks (local and remote).
Parallel operation (multiple units on same network) Yes. Supports operating in redundant mode (each unit collecting the same data) and load sharing mode (each unit collecting different data). Yes. Supports operating in redundant mode (each unit collecting the same data) and load sharing mode (each unit collecting different data).
Interaction with external systems ODBC CopperTree Kaizen, SQL server (MySQL, MS-SQL, PostgreSQL).
Upgrade Method Software download. User install. Cloud-server based auto-update. USB upgrade.
Licensing Protected by a hardware key. Various capacities are available. Protected by a software key. Various capacities are available.
BACnet Events Generated Generates TL Archival Buffer notifications None. (future planned functionality)
Response to power interruption Dependent on the host’s configuration. Auto resume capable, if configured. Preconfigured to automatically resume.
Response to TL buffer full notification Priority based TL retrieval Priority based TL retrieval