Primary air system is cooling while discharge air temperature is below setpoint
Objective/Method/Outcome
Objective: Determines if the Supply Air Temperature is below setpoint when Primary Air System is cooling
Method: Compares the supply air temperature to the setpoint to see if it was below the acceptable range while the cooling valve is open.
Outcome: Triggers an insight.
Applicable System
SAT
Description
Monitors cooling valves within primary air system units, ensuring they are closed when SAT is sufficiently below setpoint.
This rule is part of the CopperTree Standard ruleset.
Diagnosis
- Cooling may be manually overridden.
- Review control loop tuning.
- Temperature sensor may need calibration.
Message
Unit is cooling while SAT is sufficiently below setpoint.
Default Priority
Low
Rule Template
Insight Type: Energy
Trigger Type: Active High
Logic
Inputs
Input | Unit | Tags | Description |
---|---|---|---|
Supply Air Temperature | Discharge Air Temperature | The recorded supply air temperature | |
Supply Air Temperature Setpoint | Discharge Air Temperature Setpoint, Discharge Air Temperature Cooling Setpoint | The ideal supply air temperature | |
Cooling Valve | Discharge Air Cooling Command | The status of the discharge air cooling status | |
Supply Air Temperature Deadband | ° | ||
Threshold – Weekly Hours of Faulty Operation | The minimum hour of fault that can trigger an insight |
Notes
Default Values:
- Supply Air Temperature Deadband [°]: 2
- Threshold – Weekly Hours of Faulty Operation: 8