Cooling is active when zone temperature is below setpoint

Objective/Method/Outcome

Objective: Determines if the cooling is active when the zone temperature is below the setpoint.

Method: Compares the recorded air temperature to the acceptable range of temperature, if it is below the threshold, while the cooling system is on, the cost per hour of the fault is used to project potential savings, and insight is triggered.

Outcome: Calculates the potential savings, and triggers an insight.

Description

Determines if cooling is active when zone temperature is below setpoint of 1°. Insight is triggered when this occurs for greater than 2 hours in a week.

This rule is part of the CopperTree Standard ruleset.

Default Priority

Medium

Diagnosis

Review sequence of operation and program logic.

Message

Review sequence of operation and program logic.

Rule Template

Insight Type: Fault Detection

Trigger Type: Active High

Logic

Logic used to determine if cooling is active when zone temperature is below setpoint

Inputs

Input Unit Tags Description
Cooling Status    Room Cooling Command, Discharge Air Cooling Command The recorded room cooling system status
Room Temperature   Room Temperature The recorded room temperature
Const. – Acceptable Weekly Threshold Hrs   The weekly acceptable hours of room cooling system operating while recorded temperature is below setpoint.
Room Temperature Setpoint   Room Active Cooling Setpoint, Room Cooling Setpoint The ideal or predetermined room temperature
Cost per hour $   The base cost of fault per hour
Days of operation annually     The days the unit is operational to determine the annual cost of fault
Setpoint Deadband °   The acceptable variation from setpoint

Notes

Default Thresholds:

  • Setpoint Deadband: 1.5°
  • Days of operation annually: 185
  • Acceptable Weekly Threshold [hrs]: 2
  • Cost per Hour [$]: 0