Fume hood in Emergency Purge Mode for longer than expected
Objective/Method/Outcome
Objective: Determines if the Emergency Purge Mode for Fume Hood is on for more than 8 hours a day.
Method: Monitors the Emergency Purge Mode and checks the amount of time Purge Mode was ON.
Outcome: If the Purge Mode is on for longer than acceptable, an insight is generated.
Applicable System
Fume Hood
Description
Monitor the Emergency Purge Mode TL and generate an Insight if Purge Mode is ON for more than 8 hours a week.
This rule is part of the CopperTree Standard rule-set.
Diagnosis
- Purge Mode may be manual. Review control.
Message
Emergency Purge Mode is ON for a prolonged period of time. Please review control.
Rule Template
Insight Type: Fault Detection
Trigger Type: Active High
Default Priority
High
Logic
Inputs
Input | Unit | Tags | Description |
---|---|---|---|
Emergency Purge Mode | Emergency Purge Mode | Emergency Purge Mode for the hood | |
Insight Threshold – Allowable Hours | Hr | The acceptable amount of time the Purge Mode can be ON without triggering an insight |
Notes
Defaults Used:
Threshold: Acceptable Weekly Hours High Limit for Emergency Purge Mode Operation = 8 hours