Fume hood sash open during unoccupied hours
Objective/Method/Outcome
Objective: Determines if sash is open for more than the acceptable amount of time.
Method: Checks if the sash is open for more than the acceptable amount of time by comparing the position of the sash and threshold during unoccupied hours.
Outcome: Creates a CTL and insight if the sash is open during unoccupied hours
Applicable System
Fume Hood
Description
Monitor the Sash Position TL and generate an Insight if Sash is open during unoccupied hours for more than 8 hours a week.
This rule is part of the CopperTree Standard rule-set.
Diagnosis
- Sash position may be in manual. Review control.
- Contact Fume Hood operator to review Sash open/close levels.
Message
Sash is open during unoccupied hours. Please review control.
Rule Template
Insight Type: Fault Detection
Trigger Type: Active High
Default Priority
High
Logic
Input
Input
Unit
Tags
Description
Sash Position
Inches
Vertical SASH Position
The position of the Sash
Insight Threshold – Allowable Hours
Hours
The maximum amount of time the sash can be open without generating an insight
Threshold – Sash Open
Inches
The minimum vertical position of the sash to classify it as open
Occupancy
Room Occupied
Notes
Defaults Used:
- Constant – Sash Open Threshold [Inches] – 4 inches
- Constant – Threshold: Weekly Hours of Faulty Operation – 8 hours