Health Compliance Package – Chilled water valve consistently 100% open

Objective/Method/Outcome

Objective: Determines if the hot water valve is consistently 100% open during operational hours.

Method: Compares the hot water valve command to the error threshold to find the hours during which the value is open at 100%. This is compared to the hours of operation to determine if the valve is consistently at full capacity and find the avoidable cost of running the system at 100%.

Outcome: The rule triggers an insight and calculates potential savings.

Applicable System

CWS

Description

Monitor valve position TL and determine if the valve is constantly at 100%. Calculate the percentage of active hours that valve is at 100%.

This rule is part of the CopperTree Standard rule-set.

Diagnosis

  1. Valve could be manually overridden.
  2. Valve could be stuck open.

Message

The chilled water valve is consistently 100% open.

Rule Template

Insight Type: Fault Detection

Trigger Type: Active High

Logic

Logic used to determine chilled water valve is consistently 100% open

Inputs

Input Unit Tags Description
Enabled Room Occupied, Discharge Air Fan Status, Discharge Air Fan Command
Acceptable Weekly Threshold % The maximum time the fan can be at 100% without triggering an insight
Valve Error Threshold  % The acceptable error in the value of hot water valve command
Cost per hour Hr The cost of running the system
Days of operation annually The number of days the unit is operational to project annual potential savings
CHW Valve Discharge Air Cooling Command The hot water valve command value