Health Compliance Package – Domestic Hot Water Flow Temperature Outside Range
Objective/Method/Outcome
Objective: Determines if the domestic water temperature is within the acceptable range.
Method: Checks if the water temperature in outside temperature range for more than the acceptable amount of time
Outcome: If the temperature is outside the acceptable range an insight is generated.
Applicable System
HWS
Description
Monitors DHW Flow Temperature to ensure it is within 50-70 °C to prevent legionella growth.
This rule is part of the CopperTree Standard rule-set.
Diagnosis
- Temperature sensors may need calibration.
- Review programming logic.
Message
Domestic Hot Water Flow Temperature is outside acceptable range.
Rule Template
Insight Type: Fault Detection
Trigger Type: Active High
Default Priority
Medium
Logic
Inputs
Input
Unit
Tags
Description
DHW Flow Temperature
°C/°F
Domestic Hot Water Supply Temperature
Recorded domestic hot water temperature
Threshold – Hours Outside Temperature Range
Hr
Minimum hours outside of the range that triggers insight
Low-Temperature Limit
°C/ °F
Lower limit of temperature range
High-Temperature Limit
°C/ °F
Upper limit of temperature limit
Notes
Default Thresholds:
- Hours Outside Temperature Range: 2
- Low-Temperature Limit [°C]: 50°C or 122 °F
- High-Temperature Limit [°C]: 70°C or 158 °F