Health Compliance Package – Hot water valve consistently 100% open
Objective/Method/Outcome
Objective: Determines if the hot water valve is consistently 100% open during operational hours.
Method: Compares the hot water valve command to the error threshold to find the hours during which the value is open at 100%. This is compared to the hours of operation to determine if the valve is consistently at full capacity and find the avoidable cost of running the system at 100%.
Outcome: The rule triggers an insight and calculates potential savings.
Applicable System
DAF
Description
Monitor valve position TL and determine if the valve is constantly at 100%. Calculate the percentage of active hours that valve is at 100%.
This rule is part of the CopperTree Standard rule-set.
Diagnosis
- Valve could be manually overridden.
- Valve could be stuck open.
Message
Hot water valve is consistently 100% open.
Rule Template
Insight Type: Fault Detection
Trigger Type: Active High
Default Priority
Medium
Logic
Inputs
Input
Unit
Tags
Description
Enabled
Discharge Air Fan Status, Discharge Air Fan Command
The recorded status of DAF
Acceptable Weekly Threshold
%
The maximum time the fan can be at 100% without triggering an insight
Valve Error Threshold
%
The acceptable error in the value of hot water valve command
Cost per hour
$
The cost of running the system
Days of operation annually
The number of days the unit is operational to project annual potential savings
HW Valve
Discharge Air Heating Command
The hot water valve command value