Health Compliance Package – Overall Cooling Saturation

Objective/Method/Outcome

Objective: Determines the average cooling valve position across the AHUs.

Method: Calculates the average valve position by taking the sum of CCV across all AHUs are taken and divided by the number of AHUs. This is used to calculate the weekly hours of fault.

Outcome: Triggers an insight.

Description

Calculates average cooling valve position across all AHUs, and generates an insight if the average position is higher than the threshold.

Default Priority

Medium

Diagnosis

  1. Review cooling control on AHUs including whether valves are manually overridden.

Message

The overall cooling system is saturated, the average cooling valve position is above the threshold.

Rule Template

Insight Type: Fault Detection

Trigger Type: Active High

Logic

Logic for determining if overall cooling is saturated

Inputs

Input Unit Tags Description
Average Valve Position Threshold % The acceptable limit of valve position
Threshold – Weekly Hours of Saturation hr The acceptable hours of fault
AHU1 CCV The recorded AHU position
AHU2 CCV
AHU3 CCV
AHU4 CCV
AHU5 CCV
AHU6 CCV
AHU7 CCV
AHU8 CCV
AHU9 CCV
AHU10 CCV
AHU Count The number of AHUs