Heating and Cooling Simultaneously
Objective/Method/Outcome
Objective: Determines if a heating and cooling control sequence overlap exists.
Method: Checks if the HCV and the CCV are both open while the unit is on.
Outcome: Generates an insight if the amount of time the HCV and CCV are open simultaneously in a week exceeds the allowable hours threshold.
Description
Determine if a heating and cooling control sequence overlap exists by checking if the heating coil valve and the cooling coil valve are both open while the unit is on.
Default Priority
High
Diagnosis
- Error in control sequence. Review and modify programmed sequence of operation.
- Automatic control has been overridden. Revert equipment back to automatic control.
Message
The heating coil valve and cooling coil valve are simultaneously open for over 4 hours in the week. Review and modify programmed sequence of operation.
Rule Template Type
Insight Type: Fault Detection
Trigger Type: Active High
Logic
Inputs
Inputs | Units | Default Value | Tags | Description |
---|---|---|---|---|
Cooling Coil Valve | % | cmd, cool, water, valve | Cooling coil valve position (command or feedback) | |
Heating Coil Valve | % | cmd, heat, water, valve | Heating coil valve position (command or feedback) | |
Equipment Status | fan, status|cmd | Unit on status. Alternatively, building occupancy can be used | ||
Const. – Valve Open Threshold | % | 2 | Value above which the coil valve is considered open | |
Const. – Allowable Hours per Week | hrs | 4 | The acceptable hours of overlap per week |
Notes
Not valid for systems using the cooling coil for de-humidification as well as cooling.Default logic flow is designed for % open, where the CCV/HCV is considered open beyond 2%Default Constants:
- Const. – Valve Open Threshold [%]: 2
- Const. – Acceptable Hours per Week [hrs]: 4
CTL Generated:
- Weekly Hours CCV/HCV Overlap