Supply air temperature is modulating excessively
Objective/Method/Outcome
Objective: Determines if Supply Air Temperature is changing excessively
Method: Monitors the recorded Supply Air Temperature to determine if it is changing, the absolute values of the change are added and the daily average daily change during occupied hours is found.
Outcome: Triggers an insight.
Description
Monitors supply air temperature to determine if it is modulating excessively. This rule is part of the CopperTree Standard ruleset.
Default Priority
Low
Diagnosis
- Input sensor(s) faulty or miscalibration. Verify input sensor(s) operation.
- Error in control sequence. Review and modify programmed sequence of operation.
- Issue with control loop. Review and modify controller tuning parameters.
Message
Supply air temperature is modulating excessively.
Rule Template
Insight Type: Fault Detection
Trigger Type: Active High
Logic
Inputs
Input | Unit | Tags | Description |
---|---|---|---|
Discharge Air Temperature | Discharge Air Temperature | The recorded DAT | |
AHU Status | Discharge Air Fan Status, Discharge Air Fan Command | The status of the air handling unit | |
Threshold – Average Temperature Change | ° | The threshold of temperature change that can trigger insight |
Notes
Default Value:
Threshold Average Temperature Change: 6°F or 4°C