Health Compliance Package – Zone Temperature is outside the acceptable range
Objective/Method/Outcome
Objective: Determines if the zone temperature is outside the set temperature for more than the acceptable time
Method: Checks if the zone temperature is outside the set value for more than 1.5 hours and determines an urgency score depending on the level of variation of temperature from the acceptable range and the amount of time it was outside of the range.
Outcome: Creates an insight and assigns an urgency score.
Applicable System
VAV, HP, FCU, UV, UH, RAD, RHT
Description
Setpoint adherence rule: Reading is outside the established comfort range during occupancy. This rule is part of the CopperTree Standard rule-set.
Diagnosis
- Verify sensor location.
- Verify sensor has power.
- Verify reading in BMS.
- Replace if the sensor is broken.
Message
The zone temperature sensor is outside the established comfort range during occupancy. This may negatively impact comfort or energy efficiency.
Rule Template Type
Insight Type: Fault Detection
Trigger Type: Active High
Default Priority
Low
Logic
Inputs
Input
Unit
Tags
Description
Room Temperature
°C/ °F
Room Temperature
The recorded room temperature
Temp Low Limit
°C/ °F
Lower limit of temperature range
Threshold – Comfort Impact_Weekly
%
Upper limit of the impact of this rule on Building Comfort
Temp High Limit
°C/ °F
High limit of temperature range
Threshold – Max Degrees Out of Range
°C/ °F
Maximum temperature out of range that can be used for calculating score
Threshold – Urgency Score Weekly Max
%
Maximum urgency score for rule
Temp Min Limit
°C/ °F
Minimum temperature out of range that is can be used for calculating score
Temp Max Limit
°C/ °F
Maximum temperature that is used for calculating score
Daily Hours Threshold
Hr
The acceptable amount of time daily that the temperature is out of range
Room Temperature Setpoint
°C/ °F
Room Setpoint
Room temperature set point
Constant – Temperature Deadband
°C/ °F
The acceptable temperature outside range
Threshold – Weekly Acceptable
°*Hr
Weekly acceptable temperature outside the range
Occupancy
Room Occupied, Discharge Air Fan Command, Discharge Air Fan Status
Building occupancy
Notes
Default Thresholds:
- Temp Low Limit: 15°C or 55°F
- Temp Min Limit : 0°C or 32°F
- Temp High Limit: 25°C or 77°F
- Temp Max Limit: 40°C or 100°F
- Threshold – Comfort Impact_Weekly [%]: 50%
- Threshold – Max Degrees Out of Range (Urgency Score@100) : 5°C or 5°F
- Threshold – Urgency Score Weekly Max [%]: 20%
- Daily Hours Threshold [Hours]: 1.5 Hours
- Constant – Temperature Deadband : 1°C 1.5°F
- Threshold – Weekly Acceptable °*Hr [°*Hr]: 4°C.Hours or 6°F.Hours