Building static pressure control requires tuning
Description
This rule determines if pressure control requires tuning by comparing pressure to setpoint during active hours. This rule is part of the CopperTree Standard rule-set. (Aliased Celsius / Aliased Fahrenheit)
Diagnosis
- Input sensor(s) faulty or miscalibrated. Verify input sensor(s) operation.
- Automatic control has been overridden. Revert equipment back to automatic control.
- Issue with control loop. Review and modify controller tuning parameters.
Message
Building static pressure deviates more than 15% from its setpoint for longer than a specified threshold.
Rule Template
Insight Type: Integrity KPI
Trigger Type: Active High
Default Priority
Low
Notes
1. The rule is disabled if the pressure is less than 50% of its set point to prevent misleading scores.
Default Values: Acceptable Time Outside
Range per Week (hours): 4
Cost per Hour [$]: 0
Weeks of Operation: 52