VAV supply airflow control requires tuning

Objective/Method/Outcome

Objective: Determines if the VAV supply airflow control needs adjustment or calibration based on the airflow variance during occupied hours

Method: Calibrates the performance index and matrix based on the amount of time the airflow is outside the acceptable range during occupied hours.

Outcome: Generates an insight if AFLW is more than 15% of the setpoint for more than 4 hours

Applicable System

VAV

Desciption

Determine the performance index of a pressure control system using the amount of time the AFLW is not within the desired setpoint. Calculate the performance metric based on the total time the AFLW is not within the desired setpoint during occupied hours.

This rule is part of the CopperTree Standard rule-set.

Diagnosis

  1. Input sensor(s) faulty or miscalibration. Verify input sensor(s) operation.
  2. Automatic control has been overridden. Revert equipment back to automatic control.
  3. Issue with control loop. Review and modify controller tuning parameters.
  4. Primary air not available. Verify Air Handling Unit operation.

Message

Supply airflow deviates more than 15% from setpoint for more than 4 occupied hours per week.

Rule Template Type

Insight Type: Active High

Trigger Type: Integrity KPI

Default Priority

Low

Logic

Logic flow to determine if VAV supply airflow control needs tuning

Inputs

Input Unit Tags Decription
Airflow Discharge Air CFM The recorded the Airflow
Airflow Setpoint Discharge Air CFM Setpoint The preset Airflow setpoint
Occupancy Room Occupied, Discharge Fan Command, Discharge Fan Status
Threshold – Acceptable Time Outside Range per Week Hr The acceptable amount of time the unit can be at fault without triggering an insight
Threshold – Acceptable Airflow Variance  % The percentage of allowed air flow variation from setpoint

Notes

The rule is disabled if the AFLW is less than 50% of its set point in order to prevent misleading scores.