Determine if system occupancy is changing state too frequently
Applicable Systems
- Primary: AHU, RTU, MUA, ERV, BLR, CHLR
Objective/Method/Outcome
- Objective: Determine if operational status controlled by an on/off signal is changing status at a very high rate.
- Method: Check the number of times the equipment status has cycled on/off over the course of a day.
- Outcome: An insight is generated if the number of status changes is more than 6 cycles per day.
Logic
Sum daily(numberOfStatusChanges)
Notes
Input should be binary, preferably with a COV trend log. The primary equipment short cycling rule allows for less status changes per day than the secondary equipment short cycling rule.
Inputs
- Occ ( Binary Trend Log)*
- The occupancy trend log should be COV, to get the greatest value for this rule.
Parameters
Parameter | Expression Block Series Number | Description | Default Value (Units) |
---|---|---|---|
Max Cycles per Day | 7 | The acceptable number of unit status changes. Anything more than that time is considered a fault. | 6 (Cycles per day) |