Determine if Unit Heaters are Operating when Temperature is Above Setpoint
Applicable Systems
- Primary: UH
Objective/Method/Outcome
- Objective: Determine if unit heater is running unnecessarily, as room temperature is already above the setpoint
- Method: Examines zone temp, setpoint, and the heating command trend. If the zone temperature is above the setpoint, the unit command trend is examined, and the time the unit is on under such conditions is accumulated.
- Outcome: An insight is generated if the unit is overheating for more than 1 hour per week.
Logic
Normalized (15 min) room temperature and room temp setpoint trends are compared, and if the room temperature is above the deadbanded (1 °C) setpoint, the UH command trend is examined. The number of hours in which the heater is engaged under these conditions is accumulated over a week, and if the weekly total number of hours exceeds the threshold (1), an insight is triggered.
IF(RT > RT_SP + Deadband){ IF(UH >1){ Time_out_of_range +1 } IF(Time_out_of_range > 1){ INSIGHT } }
Description / Method
Monitors room temperature, room temperature setpoint, and Unit Heater fan status. Calculates the amount of time (weekly) when the temperature was above the setpoint, and the fan was running. {UH}
Diagnosis / Recommended Action
- Review UH sequence of operation.
- UH Fan might be manually overridden.
Message
Unit Heater (UH) has been running when Room Temperature is above Room Temperature Set Point. Please review UH sequence of operation.
Notes
Generates a CTL named ‘WeeklyHours_RT>SP_FanON’.Notes: This rule template could be used for Forced Flow units as well.Default Values for Constants
- Weekly Threshold: 1
- Deadband: 1
Rule Template Type
- Insight Type: Fault Detection
- Trigger Type: Active High
Default Priority
Low
Inputs
Inputs | Units | Tags | Description |
---|---|---|---|
Room Temperature | °C/°F | room|zone,temperature,sensor,air | Room Temperature being Examined |
Room Temperature Set Point | °C/°F | room|zone,temperature,sp,air | Setpoint of room in question |
Fan Status | 0/1 | fan,status|cmd | Status of the unit heater |
Constants
Inputs | Units | Default Value | Description |
---|---|---|---|
Weekly Threshold | hr | 1 | Number of hours condition can persist in order for insight to trigger |
Deadband | °C/°F | 1 | Amount the room temp is allowed to rise above the setpoint without condition becoming true |
Output Calculated Trend Logs
Output CTL | Units | Frequency | Description |
---|---|---|---|
WeeklyHours_RT_Greater_Than_SP_FanON | hr | weekly | Weekly number of hours unit is over-heating |