NIST APAR12 – Supply air temp should be less than return air temp (Mode 3 – Mech. Cooling w/100% OA)

Applicable Systems

  • NISTAPAR: APAR12
  • Primary: AHU, RTU, MUA, ERV

Objective/Method/Outcome

  • Objective: Indicates that the supply air temperature is greater than the return air temperatures while the unit is in Mode 3 (Mechanical Cooling w/100% OA)
  • Method: Check if the SAT is more than the RAT for over 8 occupied hours per week while the unit is in Mode 3.
  • Outcome: An insight is generated when the SAT is more than the RAT for over 8 occupied hours per week while the unit is in Mode 3.

Logic

If (SAT > RAT + Temperature Threshold - Temperature Rise Over Fan) { return true; }
NIST APAR12 – Supply air temp should be less than return air temp (Mode 3 – Mech. Cooling w/100% OA)

Inputs

  • RAT {sensor, return, air, temp} (Real Trend Log)
  • SAT {sensor, discharge, air, temp} (Real Trend Log)
  • AHU_MODE_CTL {ahu, mode} (Real Trend Log)

Parameters

Parameter Expression Block Series Number Description Default Value (Units)
Const- Temperature Rise Over Fan 31 The estimated air temperature rise over the fan 1.1 (C)
Temperature Threshold 30 This is the minimum temperature difference between OAT and RAT needed to enable the rule. This value is recommended by NIST. 2 (C)
Acceptable Hours per Week 33 The amount of time that this error is allowable for the unit per week. Anything more than that time is considered a fault. 8 (h)