NIST APAR17 – Supply air temp should be less than return air temp (Mode 4 – Mech. Cooling w/min OA)

Applicable Systems

  • NISTAPAR: APAR17
  • Primary: AHU, RTU, MUA, ERV

Objective/Method/Outcome

  • Objective: Indicates that the supply air temperature is greater than the return air temperatures while the unit is in Mode 4 (Mechanical Cooling w/min OA).
  • Method: Check if the SAT is more than the RAT for over 8 occupied hours per week while the unit is in Mode 4.
  • Outcome: An insight is generated when the SAT is more than the RAT for over 8 occupied hours per week while the unit is in Mode 4.

Logic

If (SAT > RAT - Temperature rise over fan + Temperature Threshold) { return true; }
NIST APAR17 – Supply air temp should be less than return air temp (Mode 4 – Mech. Cooling w/min OA)

Inputs

  • SAT {sat, ahu} (Real Trend Log)
  • RAT {rat, ahu} (Real Trend Log)
  • AHU_MODE_CTL {ahu, apar mode} (Real Trend Log)

Parameters

Parameter Expression Block Series Number Description Default Value (Units)
Const- Temperature Rise Over Fan 31 The estimated air temperature rise over the fan. 1.1 (C)
Temperature Threshold 30 This is the minimum temperature difference between OAT and RAT needed to enable the rule. 2 (C)
Acceptable Hours per Week 33 The amount of time that this error is allowable for the unit per week. Anything more than that time is considered a fault. 8 (h)