NIST APAR24 – Cooling/mixed air damper control is overlapping (Mode 5 – Unknown Occupied Mode)
Applicable Systems
NISTAPAR: APAR24
Primary: AHU, RTU, MUA, ERV
Objective/Method/Outcome
Objective: Indicates that the CCV is open while the MAD is modulating during occupied hours.
Method: Check if the CCV is open while the MAD is modulating for over 8 occupied hours per week while the unit is in Mode 5.
Outcome: An insight is generated when the CCV is open while the MAD is modulating for over 8 occupied hours per week while the unit is in Mode 5.
Logic
If( MAD > 20% Modulating; Temperature Threshold && CCV > 2% Open ) { return true; }
Inputs
CCV {cmd, cool, water, valve} (Real Trend Log)
AHU_MODE_CTL {ahu, mode} (Real Trend Log)
MAD {cmd, mixed, air, damper} (Real Trend Log)
Parameters
Parameter
Expression Block Series Number
Description
Default Value (Units)
Const – MAD min
81
The minimum damper position to be considered open
20 (%)
CCV Error Threshold
70
The movement tolerance of the CCV. This is used to define when the valve is open -everything above the formula (100 – CCV Error Threshold) is considered saturated.
0 (%)
Const – Damper signal threshold
82
The movement tolerance of the MAD.
2 (%)
Acceptable Hours per Week
73
The amount of time that this error is allowable for the unit per week. Anything more than that time is considered a fault.