Applicable Systems
- NISTAPAR: APAR28
- Primary: AHU, RTU, MUA, ERV
Objective/Method/Outcome
- Objective: ndicates that the AHU mode of operation state is changing too rapidly.
- Method: Counts the number of chenges in modes of operation per hour.
- Outcome: An insight is generated when the number of changes in modes of operation is more than 3 times per hour.
Logic
If (Mode changes per Hour > Max number of changes) { return true; }
- AHU_MODE_CTL {ahu, mode} (Real Trend Log)
Parameters
Parameter |
Expression Block Series Number |
Description |
Default Value (Units) |
Parameter |
Expression Block Series Number |
Description |
Default Value (Units) |
Max number of changes allowed per hour |
4 |
The amount of number of changes allowable for the unit per hour. Anything more than that time is considered a fault. |
12 (h) |