Applicable Systems
- NISTAPAR: APAR8
- Primary: AHU, RTU, MUA, ERV
Objective/Method/Outcome
- Objective: Indicates that the OAT is too low for the AHU to be running in Mode 3 (Mech. Cooling w/100% OA)
- Method: Check if the OAT is less than the SAT_SP for over 8 occupied hours per week while the unit is in Mode 3
- Outcome: An insight is generated when the OAT is less than the SAT_SP for over 8 occupied hours per week while the unit is in Mode 3
Logic
If OAT > (SAT - Temperature Rise Over Fan - Temperature Threshold) { return true; }
- SAT_SP {sp, discharge, air, temp} (Real Trend Log)
- OAT {sensor, outdoor, air, temp} (Real Trend Log)
- AHU_MODE_CTL {ahu, mode} (Real Trend Log)
Parameters
Parameter |
Expression Block Series Number |
Description |
Default Value (Units) |
Temperature Threshold |
74 |
This is the minimum temperature difference between OAT and SAT needed to enable the rule.This value is recommended by NIST. |
2 (C) |
Const – Temperature Rise Over Fan |
73 |
The estimated air temperature rise over the fan |
1.1 (C) |
Acceptable Hours per Week |
77 |
The amount of time that this error is allowable for the unit per week. Anything more than that time is considered a fault. |
8 (h) |