JACE Configuration (Niagara 4, AX, Honeywell Spyder)

Device estimation: 7 Stations on the same network per K-Link. Each network will require a separate Edge Device.

Getting Started

  • Network IP information here
  • Station login credentials (username and password don’t need admin credentials)
  • Must have user created on all JACE Stations
  • Overview of user settings: read-only(“1=r”), NAV=null, Type=” Default HX”, Applet Reload on Hyperlink= ”false”, Force Password Reset= ”false”, Select “Never Expires” radio button.
  • Station Settings: WebService: Enabled= “true”, Authentication Scheme= “Basic”

Overview: CopperTree leverages the HX Profile when when communicating with any Niagara-AX master controller. Many control manufacturers white label the “Tridium Jace” master controller.

Detailed instructions

Creating a CopperTree Profile

Each JACE Station NOT each AX Workstation needs to have a CopperTree user profile. Follow the instructions below on how to create a new user.1. Log into your JACE Station as an ADMIN2. Navigate to the User Manager tab

JACE3. Create a CopperTree user profile
  1. Click the new user button.
  2. Fill out the username and password. Contact Customer Solutions at [email protected]
  3. Click OK when you are done and the CopperTree user should show up in the User management window.

4. Log into your JACE Station as an admin

  • Confirm that there is an existing user for CopperTree. This user needs to be created for every JACE station, not the AX workstations.
  • Set the station settings as shown in the image above.
    1. Permissions should be set to Operator Read Only. The permission mask is “1=r”
    2. The NAV File should be set to “null”
    3. The NAV File type should be set to Default HX
    4. The Applet Reload On Hyperlink under Default Web Profile should be set to “false”.
    5. The Force Password Reset should be set to “false”.
    6. The Never Expires option under Password Expirations should be set to true.
CopperTree User

Configuring a JACE Station

  • Under the WebService tab on firm, ensure that the settings are shown as in the image below.
    • Webservice enabled should be set to “true”
    • The authentication scheme should be set to “Basic”
JACE Configuration