CopperCube-Historian Comparison

Description

The table below outlines the differences in the feature sets offered by CopperCube and Historian. If you need more clarification about any of these features, Delta Controls, the manufacturer of the CopperCube, will be your best contact.

FeatureHistorianCopperCube
Type of ProductSoftware. User installed Windows application. User supplies host computer and host Database.Stand-alone hardware appliance
Mounting OptionsIT based (requires a Windows computer or Virtual Machine). Typically, one instance, located in a central IT location.Flexible. Typically one per building. Either installed alongside controllers (and powered with 24 VAC) or in any location with standard wall outlet (and powered with 120/240 VAC).
Archiving CapacityUp to a maximum of 10,000 TLsUp to a maximum of 5000 TLs
Types of data collectedBACnet Trend logs, BACnet Events, BACnet Access Control EventsBACnet Trend logs.
[Sent to Kaizen, but not stored] BACnet Objects, BACnet Events and BACnet Controller Database backups.
User InterfaceNone. Use enteliWEB or ORCAviewPrimary: built-in web-based GUI (configuration).
Secondary: Coppertree Kaizen and enteliWEB
Methods to view Trend log dataenteliWEB and ORCAviewCoppertree Kaizen, enteliWEB, CopperCube GUI
Methods to access raw Trend log dataPull data: via ODBC, direct SQL Queries, and BACnet ReadRange servicesPull data: via API (CSV, JSON formats).
Push data: via send to CopperTree Kaizen Vault, and send to external SQL server
Backup and Restore CapabilityRelies on host database system (MySQL, MS SQL, Backup) and/or Windows backup utilities.Built in backup and restore solution to external USB disk.
Multi-site capableNo. Single BACnet network or WAN required.Yes. Supports simultaneous data collection from multiple BACnet networks (local and remote).
Parallel operation (multiple units on same network)Yes. Supports operating in redundant mode (each unit collecting the same data) and load sharing mode (each unit collecting different data).Yes. Supports operating in redundant mode (each unit collecting the same data) and load sharing mode (each unit collecting different data).
Interaction with external systemsODBCCopperTree Kaizen, SQL server (MySQL, MS-SQL, PostgreSQL).
Upgrade MethodSoftware download. User install.Cloud-server based auto-update. USB upgrade.
LicensingProtected by a hardware key. Various capacities are available.Protected by a software key. Various capacities are available.
BACnet Events GeneratedGenerates TL Archival Buffer notificationsNone. (future planned functionality)
Response to power interruptionDependent on the host’s configuration. Auto resume capable, if configured.Preconfigured to automatically resume.
Response to TL buffer full notificationPriority based TL retrievalPriority based TL retrieval