KbA0027: CopperCube Version 1.11 Patch

Description

When using CopperCube and enteliWEB, there is an issue in the representation of how meters are being identified. enteliWEB 2.2 by default will identify the meter using a property name of Value. The CopperCube stores these properties using the name Present_Value. This fix allows CopperCube to provide the data to enteliWEB when it requests either property name.

This is a patch only for version 1.11 CopperCubes and not other versions.

Patch process

enteliWEB Version
Please confirm that your enteliWEB 2.2 servers has been patched to the most recent version (version 2.2.472 or later)CopperCube upgrade

  1. Format a USB memory stick with the FAT32 format.
  2. Download this file CopperCube.1.11.1175-20150408.zip (6Mb) file.
  3. Extract the zip file to the root of the USB device. The USB drive should now have a structure like this: upgrade_folder_structure.png
  1. Plug the USB stick into CopperCube.
  2. You will hear a low-high beep telling you that the CopperCube recognized the device.
  3. Within 30 seconds you should hear a second beep (this time: high then low) to tell you the update is done
  4. Leave the USB stick in, and the CopperCube will reboot itself
  5. On reboot, the CopperCube will play a tune.
  6. Remove USB device
  7. Verify that the Status page says version 1.11.1175

Congratulations your CopperCube has been upgraded.