Objective/Method/Outcome
Objective: Determines if the command and status signals of cooling tower fan are matching
Method: Compares the Command and Status to check if the command and status signals are active at the same time, to find out the hours of fault.
Outcome: Trigger an insight if the hours of fault are greater than the acceptable hours of fault.
Description
Compares the status and command signals to determine if there is a mismatch.
This rule is part of the CopperTree Standard ruleset.
Default Priority
High
Diagnosis
- Check if equipment is manually overridden.
- Check interfacing relays.
- Check status sensors.
Message
Cooling tower fan command-status signals do not match. Please investigate unit control.
Rule Template
Insight Type: Fault Detection
Trigger Type: Active High
Logic
Inputs
Input | Unit | Tag | Description |
---|---|---|---|
Command | Cooling Tower Fan Command | The recorded Cooling Tower Fan command | |
Status | Cooling Tower Fan Status | The recorded Cooling Tower Fan status | |
Acceptable Hours of Fault per Week | The allowable hours of fault | ||
Cost per Hour | $ | The cost per hour of the fault | |
Days of operation annually | The estimated yearly days of operation to project annual savings |