Effective setpoint (Heating and Cooling) is unchanged between occupied and unoccupied schedule

Objective/ Method/Outcome

Objective: Determines if effective temperature setpoint remains unchanged when occupancy schedule changes.

Method: Compares the changes in occupancy schedule to the changes in effective temperature setpoint. If the effective temperature setpoint remains unchanged when the occupancy schedule changes, the hours of faulty operation are calculated.

Outcome: This rule generates an insight if the Weekly Hours of Faulty Operation exceeds the acceptable weekly threshold.

Description

Reference: ASHRAE90.1-6.4.3.3.2

This rule determines if the effective heating temperature setpoint is unchanged between occupied and unoccupied schedule. An insight will be generated if occupied effective heating temperature setpoint does not change during unoccupied hours by the specified deadband.

This rule is part of the CopperTree Standard rule-set. (Aliased Celsius / Aliased Fahrenheit)

Default Priority

Medium

Diagnosis

1. Verify if active setpoint resets based on building schedule.

2. Verify if unoccupied setpoint value is correct.

Message

Unoccupied setback control might be missing.

Rule Template

Insight Type: Fault Detection

Trigger Type: Active High

Notes

1. Expected values for “Occupancy” inputs are “0” or “1”.

Default Values:

Const. – Acceptable Weekly Hours of Faulty Operation [Hours]: 8

CTLs:

Heating SP Unchanged When Unoccupied – Hours of Faulty Operation (CUSUM)

Heating SP Unchanged When Unoccupied  – Weekly Hours of Faulty Operation (KPI)