Objective/Method/Outcome
Objective: Determines if heating is sufficient.
Method: Compares the heating command to the valve error threshold to determine if the valve is at 100%. Determines if SAT is heating the sum of the setpoint and the acceptable deadband. This is used to filter the amount of time temperature is below the acceptable range while the heating command is at 100%. Another filter is applied to determine if the AHU was active during these hours. This is used to calculate the weekly hours of fault operation.
Outcome: Calculates an Integrity KPI and triggers an insight.
Description
Monitor valve position TL and determine if the valve is constantly at 100% while SAT is not satisfying setpoint requirements.
This rule is part of the CopperTree Standard rule-set.
Default Priority
Medium
Diagnosis
- Review temperature sensor calibration.
- Heating may be insufficient.
Message
Heating may be insufficient as valve is 100% open while SAT can not satisfy setpoint requirements.
Rule Template
Insight Type: Fault Detection
Trigger Type: Active High
Logic
Inputs
Input | Unit | Tags | Description |
---|---|---|---|
AHU Status | Discharge Air Fan Status, Discharge Air Fan Command | The recorded status of the AHU | |
Threshold – Weekly Hours | The minimum hours of fault that can trigger an insight | ||
SAT | Discharge Air Temperature | The recorded SAT | |
SAT SP | Discharge Air Temperature Setpoint | The preset/ideal SAT | |
Temperature Setpoint Deadband | The allowable deviation from temperature setpoint | ||
Heating Valve | Discharge Air Heating Command | The recorded Heating Command |
Notes
Default Thresholds:
- Temperature Setpoint Deadband: 2°
- Threshold – Weekly Hours: 8