Below is a list of all of Kaizen’s Infrastructure Rules. These are in every Building by default.
CopperCube
Name
Default Priority
Objective
CopperCube Offline
High
A lack of regular heartbeats indicates CopperCube communication problems. Find CopperCubes whose last report is more than 60 minutes old.
Not sending BACnet Objects
High
Objects are the basis of Golden Standards. A lack of objects indicates data collection or transmission problems. Find CopperCubes reporting no objects sent yesterday & today.
Not sending trend log updates
High
Trends are the basis of Kaizen analytics. A lack of trends indicates data collection or transmission problems. Find CopperCubes reporting no trends sent yesterday & today.
Volume of objects has changed significantly
Med
A large change in the #of objects sent indicates communication problems or configuration changes. Find CopperCubes whose daily object volume differs more than 5% from its 7 day moving average.
Volume of trends has changed significantly
Med
A large change in the #of trends sent indicates communication problems or configuration changes. Find CopperCubes whose daily trend volume differs more than 5% from its 7 day moving average.
Controllers (DEV)
Name
Objective
Method
Threshold
Range
High Reset Count
High device reset counts indicate serious controller, database or network problems.
Find controllers with Reset counts > X
25 Resets
25 – 250 Devices max @ 255
Full Database
Low Database memory causes inconsistent operational behaviour and can impact Firmware upgrades.
Find controllers with less than X% free memory
15%
5% – 15%
Low Memory
Low working memory causes inconsistent operational behaviour and can prevent proper alarming.