Fume hood airflow is exceeding setpoint

Objective/Method/Outcome

Objective: Determines if the fume hood airflow is exceeding setpoint for more than the acceptable amount of time.

Method: Compares the Exhaust Airflow to the setpoint to determine if the Airflow is above the Airflow threshold during occupied hours.

Outcome: Creates a Fault Detection insight and a CTL for Weekly hours above setpoint.

Applicable System

Fume Hood

Description

Fume hood airflow is exceeding setpoint, which may result in excess energy consumption.

This rule is part of the CopperTree Standard rule-set.

Diagnosis

  1. Check fumehood control and programming logic.
  2. Review airflow sensor calibration.

Message

Fume hood airflow is exceeding setpoint, which may result in excess energy consumption.

Rule Template

Insight Type: Fault Detection

Trigger Type: Active High

Default Priority

High

Logic

Logic for determining if fume hood airflow exceeds setpoint

Inputs

InputUnitsTagsDescription
Fume Hood Exhaust AirflowExhaust Air CFMThe recorded Exhaust Air Flow
Insight Threshold – Allowable HoursHrThe minimum number of hours required to generate an insight
Fume Hood Exhaust Airflow SetpointExhaust Air CFM SetpointThe setpoint for exhaust Airflow
Fume Hood StatusFume Hood OccupancyThe recorded status of fume hood
Airflow Threshold %The minimum deviation from setpoint that triggers insight

Notes

Default Thresholds:

  • Airflow Setpoint Threshold: 10%
  • Threshold – Weekly Acceptable Hours: 8