Objective/Method/Outcome
Objective: Determines if the domestic water temperature is within the acceptable range.
Method: Checks if the water temperature in outside temperature range for more than the acceptable amount of time
Outcome: If the temperature is outside the acceptable range an insight is generated.
Applicable System
HWS
Description
Monitors DHW Flow Temperature to ensure it is within 50-70 °C to prevent legionella growth.
This rule is part of the CopperTree Standard rule-set.
Diagnosis
- Temperature sensors may need calibration.
- Review programming logic.
Message
Domestic Hot Water Flow Temperature is outside acceptable range.
Rule Template
Insight Type: Fault Detection
Trigger Type: Active High
Default Priority
Medium
Logic
Inputs
Input | Unit | Tags | Description |
---|---|---|---|
DHW Flow Temperature | °C/°F | Domestic Hot Water Supply Temperature | Recorded domestic hot water temperature |
Threshold – Hours Outside Temperature Range | Hr | Minimum hours outside of the range that triggers insight | |
Low-Temperature Limit | °C/ °F | Lower limit of temperature range | |
High-Temperature Limit | °C/ °F | Upper limit of temperature limit |
Notes
Default Thresholds:
- Hours Outside Temperature Range: 2
- Low-Temperature Limit [°C]: 50°C or 122 °F
- High-Temperature Limit [°C]: 70°C or 158 °F