Health Compliance Package – Overall Heating Saturation

Objective/Method/Outcome

Objective: Determines the average heating valve position across the AHUs.

Method: Calculates the average valve position by taking the sum of HCV across all AHUs are taken and divided by the number of AHUs. This is used to calculate the weekly hours of fault.

Outcome: Triggers an insight.

Description

Calculates average heating valve position across all AHUs, and generates an insight if the average position is higher than the threshold.

Default Priority

Medium

Diagnosis

  1. Review heating control on AHUs including whether valves are manually overridden.

Message

The overall heating system could be saturated, the average heating valve position is above the threshold.

Rule Template

Insight Type: Fault Detection

Trigger Type: Active High

Logic

Logic for determining if overall heating is saturated

Inputs

InputUnitTagsDescription
Average Valve Position Threshold%The acceptable limit of valve position
Threshold – Weekly Hours of SaturationhrThe acceptable hours of fault
AHU1 HCVThe recorded AHU position
AHU2 HCV
AHU3 HCV
AHU4 HCV
AHU5 HCV
AHU6 HCV
AHU7 HCV
AHU8 HCV
AHU9 HCV
AHU10 HCV
AHU CountThe number of AHUs