Supply air temperature is modulating excessively

Objective/Method/Outcome

Objective: Determines if Supply Air Temperature is changing excessively

Method: Monitors the recorded Supply Air Temperature to determine if it is changing, the absolute values of the change are added and the daily average daily change during occupied hours is found.

Outcome: Triggers an insight.

Description

Monitors supply air temperature to determine if it is modulating excessively. This rule is part of the CopperTree Standard ruleset.

Default Priority

Low

Diagnosis

  1. Input sensor(s) faulty or miscalibration. Verify input sensor(s) operation.
  2. Error in control sequence. Review and modify programmed sequence of operation.
  3. Issue with control loop. Review and modify controller tuning parameters.

Message

Supply air temperature is modulating excessively.

Rule Template

Insight Type: Fault Detection

Trigger Type: Active High

Logic

Logic used to determine if SAT is modulating excessively

Inputs

InputUnitTagsDescription
Discharge Air Temperature Discharge Air TemperatureThe recorded DAT
AHU Status Discharge Air Fan Status, Discharge Air Fan CommandThe status of the air handling unit
Threshold – Average Temperature Change° The threshold of temperature change that can trigger insight

Notes

Default Value:

Threshold  Average Temperature Change: 6°F or 4°C