Enhanced Prioritization – Boiler operating above lockout temperature

Objective/Method/Outcome

Objective: Determines if boiler is operational when the temperature of OAT is above the lockout temperature

Method: Checks the boiler is enabled, and determines the moving average of OAT. If the Boiler is enabled when the 4 hour moving average of the system is above the Boiler enable setpoint, an insight is triggered and the potential savings is projected by calculating the hours of fault and the cost of fault per hour.

Outcome: Triggers an insight, calculates the potential savings and the weekly energy impact.

Description

Determines if the boiler is operating when the heating plant may not be required, while OAT is above lockout temperature. Potential Savings can be calculated by modifying the “Cost per Hour of Operation” input.

This rule is part of the CopperTree Standard rule-set.

Default Priority

Medium

Diagnosis

  1. Boiler plant operating above OAT lockout. Verify heating plant sequence of operation.
  2. Automatic control has been overridden. Revert equipment back to automatic control.

Message

The boiler has been operating while the OAT is above its lockout temperature. Ensure that boiler enable is not overridden, then verify sequence of operation.

Rule Template

Insight Type: Fault Detection

Trigger Type: Active High

Logic

Logic for determining if boiler is operating above lockout template

Inputs

InputUnitTagsDescription
Boiler EnableBoiler Command, Boiler StatusThe recorded status of the boiler
Threshold – PotentialSavings Yearly$The minimum potential savings per year that can trigger an insight
Outdoor Air Temp°Outdoor Air TemperatureThe recorded outdoor air temperature
Estimated Weeks Of Boiler OperationThe estimated weeks the boiler is operational per year
Boiler Enable OAT Setpoint °C/°FThe OAT that enables the boiler
Threshold – Weekly Energy Impact %The minimum percentage of fault that can trigger an Energy Impact
Cost per Hour of Operation$The cost of fault per hour
Threshold – Weekly Hours of Faulty OperationHrThe minimum weekly faulty hours of operation that can trigger an insight

Notes

Default Values:

  • Threshold – Hours of Faulty Operation: 4
  • Boiler Enable OAT Setpoint: 65 °F or 18 °C
  • Estimated Weeks Of Boiler Operation: 26
  • Cost per Hour of Operation [$]: 0