Health Compliance Package – CO2 Concentration Analysis

Objective/Method/Outcome

Objective: Analyses the CO2 concentration

Method: Determines the occupancy of the room. Compared the recorded CO2 concentration and the CO2 setpoint. Calculates the Urgency Score and the potential savings using the hours CO2 is above the threshold and the cost of fault per hour.

Outcome: Triggers an insight, calculates potential savings and the urgency score.

Description

Measures indoor CO2 concentration during building occupancy to determine Ventilation Impact and Urgency Score.

This rule is part of the CopperTree Standard rule-set.

Insight is triggered when Ventilation Impact exceeds the weekly threshold (defined by the user). This can be changed to trigger on Urgency Score (based on peak CO2).

  • Ventilation Impact is the number of days (expressed in percent of total days analyzed) that the CO2 has exceeded the accepted operative during occupied hours.
  • Urgency Score indicates the magnitude of error outside the acceptable CO2 limit. A score of 100 indicates that the CO2 concentration has reached 1600ppm or more during the week during occupied hours.
  • A CTL measures the cumulative sum (CUSUM) of the number of days the accepted CO2 limit has been exceeded.

Default Priority

Medium

Diagnosis

  1. Review sensor calibration.
  2. Control program error. Verify equipment sequence of operations.

Message

CO2 concentration has been exceeded acceptable limits.

Rule Template

Insight Type: Fault Detection

Trigger Type: Active High

Logic

Logic for analyzing CO2 concentration

Inputs

InputUnitTagsDescription
CO2ppmRoom CO2, Return Air CO2The recorded concentration of CO2
Threshold – CO2 Setpoint ppmThe pre-determined setpoint for CO2
Threshold – Ventilation Impact Trigger%The minimum ventilation impact that can trigger an insight
Threshold – Urgency Score Trigger%The minimum urgency score that can trigger an insight
OccupancyRoom Occupied, Discharge Air Fan Status
Threshold – Max Acceptable CO2 ppmThe maximum allowable CO2 concentration, above which an insight is triggered
Cost per Hour$The cost of the fault per hour
Days of operation annually The days the equipment is operational per year. Used to project potential savings.

Notes

Default Values:

  • Threshold – CO2 Setpoint [ppm]: 1000
  • Threshold – Ventilation Impact Trigger [%]: 14
  • Threshold – Urgency Score Trigger [%]: 40
  • Threshold – Max Acceptable CO2 (Urgency Score @100) [ppm]: 1600