Objective/Method/Outcome
Objective: Checks for unreliable readings of Zone air CO2 sensor
Method: Checks the zone carbon dioxide reading to determine if it is out of range. The 24-hour maximum and minimum are also determined. If the maximum and minimum reading was constant or the zone carbon dioxide was constantly out of acceptable range, for more than the acceptable amount of time, an insight is triggered.
Outcome: Triggers an insight if zone air carbon dioxide sensor is determined to be faulty.
Description
Sensor validation rule: Check for unreliable readings in range and quality.
This rule is part of the CopperTree Standard ruleset.
Default Priority
Low
Diagnosis
- Verify sensor exists.
- Verify sensor has power.
- Verify reading in BMS.
- Replace if sensor is broken.
Message
Zone carbon dioxide sensor is reading outside reasonable range or is stuck on one value. This may negatively impact comfort or energy efficiency.
Rule Template
Insight Type: Fault Detection
Trigger Type: Active High
Logic
Inputs
Input | Unit | Tags | Description |
---|---|---|---|
Zone Carbon Dioxide | ppm | Room CO2 | The recorded zone carbon dioxide |
Zone Carbon Dioxide Low Limit | ppm | The lower limit of acceptable zone carbon dioxide range | |
Zone Carbon Dioxide High Limit | ppm | The upper limit of acceptable zone carbon dioxide range | |
Weekly Insight Threshold | Hr | The minimum acceptable hours of fault that can trigger an insight |
Notes
Default Thresholds:
- Zone Carbon Dioxide Low Limit [ppm]: 200 ppm
- Zone Carbon Dioxide High Limit [ppm]: 2000 ppm
- Weekly Insight Threshold [hours]: 120 hours