Applicable Systems
- Primary: AHU
Objective/Method/Outcome
- Objective: Determine if system is accidentally cooling when the outdoor air temperature is low, and the heating system is engaged.
- Method: Examine the cooling coil valve to determine if cooling is engaged, and the outdoor air temperature and the heating coil valve to see if heating is required in the building.
- Outcome: An insight is generated if there is accidental heating for more (default) 2 hours per week.
Logic
The logic flow starts with checking if the CCV and HCV are open, using the valve open threshold. The outdoor air temperature is also compared to a constant threshold, to see if the building needs cooling. If the CCV and HCV are open, and the OAT is low, the number of hours the fault occurs per week while the system is on is tallied and an insight is triggered if the condition persists for more than 2 hours per week.
IF( CCV is Open){ IF( HCV||SCV is Open){ IF(OAT < Threshold){ Count: Hours in Fault IF(Hours in Fault <= 2){ TRIGGER INSIGHT } } } }
Description / Method
Calculates the number of hours Cooling Coil Valve (CCV) is open while Outside Air Temperature (OAT) is less than the threshold (user adjustable), and Steam Control Valve or Heating Control Valve is open {MAU|AHU|RTU}This rule could be applied on makeup air units, air handling units or rooftop units that have a steam control valve, heating coil valve and cooling coil valve.
Diagnosis / Recommended Action
- Check if CCV is manually overridden
- Optimize control sequence for the unit
Message
Unit is heating and cooling simultaneously even when Outside Air Temperature is below the threshold. Ensure that valves are not manually overridden.
Notes
All timespans and thresholds are adjustable. The rule also generates one Calculated Trend Log: Daily_Hours_CCV_Open_while_Heating.Default Inputs: Outside Air Temperature Threshold [deg C] = 12 Constant – Valve Open [%] = 10 Weekly Threshold = 2
Rule Template Type
- Insight Type: Fault Detection
- Trigger Type: Active High
Default Priority
High
Inputs
Inputs | Units | Default Value | Tags | Description |
---|---|---|---|---|
Cooling Coil Valve | % | cmd, water, cool, valve | Cooling Coil Valve Trend Log | |
Outside Air Temperature | °C/°F | outside,air,temp,sensor | Outdoor Air Temperature | |
Steam Control Valve | % | cmd,heat,steam,valve | Steam control valve trend log | |
Heating Coil Valve | % | cmd, heat, water, valve | Heating coil valve trend log |
Schedule | schedule|occupied|status | AHU schedule |
Constants
Inputs | Units | Default Value | Description |
---|---|---|---|
Outside Air Temperature Threshold | °C/°F | 12 | Threshold to determine whether or not temperature is sufficiently cold for heating |
Constant – Valve Open | % | 10 | Threshold to determine if valve is open |
Weekly Threshold | 2 | Number of hours fault needs to exceed for insight to trigger |
Output Calculated Trend Logs
Output CTL | Units | Frequency | Description |
---|---|---|---|
Daily_Hours_CCV_Open_while_Heating | hours | Daily | Hours per day heating and cooling occur simultaneously |