NIST APAR13 – Cooling coil valve command is fully open and SAT error exists (Mode 3 – Mech. Cooling w/100% OA)

Applicable Systems

  • NISTAPAR: APAR13
  • Primary: AHU, RTU, MUA, ERV

Objective/Method/Outcome

  • Objective: Indicates that the cooling coil valve is fully open and the SAT is greater than the setpoint while the AHU is in Mode 3 (Mech. Cooling w/100% OA)
  • Method: Check if the SAT is more than 2 degrees above set point for over 8 occupied hours per week while the unit is in Mode 3
  • Outcome: An insight is generated when the SAT is more than 2 degrees above set point for over 8 occupied hours per week while the unit is in Mode 3

Logic

If (SAT - SAT SP > Temperature Threshold && CCV Open) { return true; }
NIST APAR13 – Cooling coil valve command is fully open and SAT error exists (Mode 3 – Mech. Cooling w/100% OA).

Inputs

  • SAT {sensor, discharge, air, temp} (Real Trend Log)
  • SAT_SP {sp, discharge, air, temp} (Real Trend Log)
  • AHU_MODE_CTL {ahu, mode} (Real Trend Log)
  • CCV {cmd, cool, water, valve } (Real Trend Log)

Parameters

ParameterExpression Block Series NumberDescriptionDefault Value (Units)
Const- CCV Error Threshold74The movement tolerance of the CCV. This is used to define when the valve is open -everything above the formula (100 – CCV Error Threshold) is considered saturated.2 (%)
Temperature Threshold75The acceptable temperature deviation from setpoint that is considered normal2 (C)
Acceptable Hours per Week60The amount of time that this error is allowable for the unit per week. Anything more than that time is considered a fault.8 (h)