NIST APAR2 – Outdoor air fraction out of acceptable range (Mode 1 – Heating)
Applicable Systems
NIST: APAR2
Primary: AHU, RTU, MUA, ERV
Objective/Method/Outcome
Objective: Indicates that the fraction of outdoor air is too high or too low while the AHU is in Mode 1 (Heating). MAT, RAT, and OAT are used to calculate the fraction of OA entering the building.
Method: Check if the the calculated OAF is not within the desired minimum OAF (30%) for more than 12 occupied hours per week.
Outcome: An insight is generated when the calculated OAF is not within the desired minimum OAF (30%) for more than 12 occupied hours per week.
Logic
If (MAT - SAT + Temperature Rise Over Fan > Temperature Threshold && HCV > 0% Open) { return true; }