NIST APAR20 – Cooling coil valve is frequently fully open (Mode 4 – Mech. Cooling w/min OA)
Applicable Systems
NISTAPAR: APAR20
Primary: AHU, RTU, MUA, ERV
Objective/Method/Outcome
Objective: Indicates that the cooling coil valve is frequently fully open while the unit is in Mode 4 (Mech. Cooling w/min OA). This rule is a warning and indicates that the system may be out of control. If APAR19 is active, this rule is suppressed.
Method: Check if the CCV is fully open for over 8 occupied hours per week while the unit is in Mode 4.
Outcome: An insight is generated when the CCV is fully open for over 8 occupied hours per week while the unit is in Mode 4.
The movement tolerance of the CCV. This is used to define when the valve is open -everything above the formula (100 – CCV Error Threshold) is considered saturated.
2 (%)
Acceptable Hours per Week
60
The amount of time that this error is allowable for the unit per week. Anything more than that time is considered a fault.