NIST APAR20 – Cooling coil valve is frequently fully open (Mode 4 – Mech. Cooling w/min OA)
Applicable Systems
NISTAPAR: APAR20
Primary: AHU, RTU, MUA, ERV
Objective/Method/Outcome
Objective: Indicates that the cooling coil valve is frequently fully open while the unit is in Mode 4 (Mech. Cooling w/min OA). This rule is a warning and indicates that the system may be out of control. If APAR19 is active, this rule is suppressed.
Method: Check if the CCV is fully open for over 8 occupied hours per week while the unit is in Mode 4.
Outcome: An insight is generated when the CCV is fully open for over 8 occupied hours per week while the unit is in Mode 4.
NIST APAR20 – Cooling coil valve is frequently fully open (Mode 4 – Mech. Cooling w/min OA)
Inputs
CCV {cmd, cool, water, valve } (Real Trend Log)
AHU_MODE_CTL {ahu, mode} (Real Trend Log)
APAR19_TRUE_CTL {apar19} (Real Trend Log)
Parameters
Parameter
Expression Block Series Number
Description
Default Value (Units)
CCV Error Threshold
74
The movement tolerance of the CCV. This is used to define when the valve is open -everything above the formula (100 – CCV Error Threshold) is considered saturated.
2 (%)
Acceptable Hours per Week
60
The amount of time that this error is allowable for the unit per week. Anything more than that time is considered a fault.