NIST APAR23 – Heating/mixed air damper control is overlapping (Mode 5 – Unknown Occupied Mode)
Applicable Systems
NISTAPAR: APAR
Primary: AHU, RTU, MUA, ERV
Objective/Method/Outcome
Objective: Indicates that the HCV and MAD are operating at the same time during occupied hours.
Method: Check if the HCV and MAD are operating at the same time for over 8 occupied hours per week while the unit is in Mode 5.
Outcome: An insight is generated when the HCV and MAD are operating at the same time for over 8 occupied hours per week while the unit is in Mode 5.
Logic
If (MAD > 20% Modulating; Temperature Threshold && HCV > 2% Open) { return true; }
Inputs
HCV {cmd, heat, water, valve } (Real Trend Log)
AHU_MODE_CTL {ahu, mode} (Real Trend Log)
MAD {cmd, mixed, air, damper} (Real Trend Log)
Parameters
Parameter
Expression Block Series Number
Description
Default Value (Units)
Const – MAD min
81
The minimum damper position to be considered open
20 (%)
HCV Error Threshold
70
The movement tolerance of the HCV. This is used to define when the valve is open -everything above the formula (100 – HCV Error Threshold) is considered saturated.
0 (%)
Const – Damper signal threshold
82
The movement tolerance of the MAD.
2 (%)
Acceptable Hours per Week
73
The amount of time that this error is allowable for the unit per week. Anything more than that time is considered a fault.