Applicable Systems
- NISTAPAR: APAR5
- Primary: AHU, RTU, MUA, ERV
Objective/Method/Outcome
- Objective: Indicates that the OAT is too high for the AHU to be running in Mode 2 (Cooling w/ OA).
- Method: Check if the OAT is greater than the SAT SP for over 8 occupied hours per week while the unit is in Mode 2.
- Outcome: An insight is generated when the OAT is greater than the SAT SP for over 8 occupied hours per week while the unit is in Mode 2.
Logic
If OAT > (SAT SP - Temperature Threshold + Temperature Rise Over Fan) { return true; }
- SAT_SP {discharge, air, temp, setpoint} (Real Trend Log)
- OAT {sensor, outdoor, air, temp} (Real Trend Log)
- AHU_MODE_CTL {ahu, mode} (Real Trend Log)
Parameters
Parameter | Expression Block Series Number | Description | Default Value (Units) |
---|
Const – Temperature Rise Over Fan | 73 | The estimated air temperature rise over the fan | 1.1 (C) |
Temperature Threshold | 74 | This is the minimum temperature difference between OAT and SAT SP needed to enable the rule. | 2 (C) |
Acceptable Hours per Week | 77 | The amount of time that this error is allowable for the unit per week. Anything more than that time is considered a fault. | 8 (h) |