NIST APAR6 – Supply air temp should be less than return air temp (Mode 2 – Cooling w/OA)
Applicable Systems
NISTAPAR: APAR6
Primary: AHU, RTU, MUA, ERV
Objective/Method/Outcome
Objective: Indicates that the SAT is too high in relation to the RAT given the AHU is running in Mode 2 (Cooling w/ OA). This rule only applies when the AHU is in free cooling mode.
Method: Check if the SAT is greater than the RAT by more than 2 degrees for over 8 occupied hours per week while the unit is in Mode 2.
Outcome: An insight is generated when the SAT is greater than the RAT by more than 2 degrees for over 8 occupied hours per week while the unit is in Mode 2.
Logic
If SAT > (RAT + Temperature Threshold - Temperature Rise Over Fan) { return true; }</span>
Inputs
RAT {return, air, temp, sensor} (Real Trend Log)
SAT {sensor, supply, air, temp} (Real Trend Log)
AHU_MODE_CTL {ahu, mode} (Real Trend Log)
Parameters
Parameter
Expression Block Series Number
Description
Default Value (Units)
Temperature Threshold
74
This is the minimum temperature difference between SAT and RAT needed to enable the rule.
2 (C)
Const – Temperature Rise Over Fan
73
The estimated air temperature rise over the fan
1.1 (C)
Acceptable Hours per Week
77
The amount of time that this error is allowable for the unit per week. Anything more than that time is considered a fault.