Applicable Systems
- NISTAPAR: APAR7
- Primary: AHU, RTU, MUA, ERV
Objective/Method
- Objective: Indicates an inconsistency between supply and mixed air temperatures while the unit is in Mode 2 (Cooling w/OA)
- Method: Check if the SAT is more than +/-2 degrees from the MAT for over 8 occupied hours per week while the unit is in Mode 2
Logic
If (absolute(SAT - Temperature Rise Over Fan - MAT) > Temperature Threshold){ return true; }
- SAT {sensor, discharge, air, temp} (Real Trend Log)
- AHU_MODE_CTL {ahu, mode} (Real Trend Log)
- MAT {sensor, mixed, air, temp} (Real Trend Log)
Parameters
Parameter | Expression Block Series Number | Description | Default Value (Units) |
---|
Temperature Threshold | 30 | This is the minimum temperature difference between SAT and MAT needed to enable the rule. | 2 (C) |
Const – Temperature Rise Over Fan | 31 | The estimated air temperature rise over the fan | 1.1 (C) |
Acceptable Hours per Week | 33 | The amount of time that this error is allowable for the unit per week. Anything more than that time is considered a fault. | 8 (h) |