List of Infrastructure Insights

Description

Below is a list of all of Kaizen’s Infrastructure Rules. These are in every Building by default.

CopperCube

NameDefault PriorityObjective
CopperCube OfflineHighA lack of regular heartbeats indicates CopperCube communication problems. Find CopperCubes whose last report is more than 60 minutes old.
Not sending BACnet ObjectsHighObjects are the basis of Golden Standards. A lack of objects indicates data collection or transmission problems. Find CopperCubes reporting no objects sent yesterday & today.
Not sending trend log updatesHighTrends are the basis of Kaizen analytics. A lack of trends indicates data collection or transmission problems. Find CopperCubes reporting no trends sent yesterday & today.
Volume of objects has changed significantlyMedA large change in the #of objects sent indicates communication problems or configuration changes. Find CopperCubes whose daily object volume differs more than 5% from its 7 day moving average.
Volume of trends has changed significantlyMedA large change in the #of trends sent indicates communication problems or configuration changes. Find CopperCubes whose daily trend volume differs more than 5% from its 7 day moving average.

Controllers (DEV)

NameObjectiveMethodThresholdRange
High Reset CountHigh device reset counts indicate serious controller, database or network problems.Find controllers with Reset counts > X25 Resets25 – 250 Devices max @ 255
Full DatabaseLow Database memory causes inconsistent operational behaviour and can impact Firmware upgrades.Find controllers with less than X% free memory15%5% – 15%
Low MemoryLow working memory causes inconsistent operational behaviour and can prevent proper alarming.Find controllers with less than X% free memory15%5% – 15%
Controller In-FaultControllers In-Fault indicate devices needing immediate servicing.Find controllers reporting “Non-operational”  

Input Objects (AI,BI,MI,PI)

NameObjectiveMethod
Input UncommissionedThe commissioned flag identifies Inputs that have been tested as correctly wired and operational.Find inputs (AI, BI, PI, MI) with “Commission_Flag” = “Not Commissioned”.
Input Out-of-ServiceInputs in manual mode prevent automatic control.Find inputs (AI, BI, PI, MI) with “Out_Of_Service” = True.
Input In-FaultInputs In-Fault cannot measure their operating environment.Find inputs (AI, BI, PI, MI) reporting a “Fault” condition (in Flags).

Output Objects (AO,BO,MO)

NameObjectiveMethod
Output UncommissionedThe commissioned flag identifies Outputs that have been tested as correctly wired and operational.Find outputs (AO, BO, MO) with “CommissionFlag” = “Not Commissioned”.
Output Out-Of-ServiceOutput in manual mode prevent automatic control.Find outputs (AO, BO, MO) with “Out_Of_Service” = True.
Output In-FaultOutput In-Fault cannot make changes to their environment.Find outputs (AO, BO, MO) reporting a “Fault” condition (in Flags).

Trend Logs (TL)

NameObjectiveMethod
Trend Log Out-Of-ServiceTrend Logs in manual mode are not collecting data.Find trend logs (TL) with “Out of Service” = True.
Trend Log In-FaultTrend Logs In-Fault are not collecting data.Find trend logs (TL) reporting a “Fault” condition (in Flags).

Scheduling Objects (CAL,SCH)

NameObjectiveMethod
Calendar Out-Of-ServiceCalendars in manual prevent scheduled control of operations.Find calendars (CAL) with “Out of Service” = True.
Schedule Out-Of-ServiceSchedules in manual prevent scheduled control of operations.Find Schedules (SCH) with “Out of Service” = True.

Control Objects (CO,PG)

NameObjectiveMethod
Control Loop Out-Of-ServiceControl loops are a common form of automatic control. Control Loops in manual are disabled.Find control loops (CO) with “Out of Service” = True.
Program Out-Of-ServicePrograms (PG) are a sophisticated form of automatic control. Programs in manual are disabled.Find programs (PG) with “Out_Of_Service” = True.
Program In-FaultGCL programs In-Fault have detected errors that prevent execution.Find GCL programs (PG) reporting a “Fault” condition (in Flags).

Delta V2 (Legacy)

NameObjectiveMethod
Zone I/O UncommissionedThe commissioned flag identifies Zone I/O that have been tested as correctly wired and operational.Find Delta V2 Zone controllers (ZC) with “CommissionFlag” = “Not Commissioned
Zone Controller Out_Of_ServiceZone Controllers in manual mode impact automatic control.Find Delta V2 Zone controllers (ZC) with “Out_Of_Service” = True.
Zone Controller In-FaultZone Controllers In-Fault are not operating.Find Delta V2 Zone controllers (ZC) reporting a “Fault” condition (in Flags).