Enhanced Prioritization – Determine if boiler is operating when OAT is above lockout temperature

Applicable Systems

  • Primary: BLR

Description / Method

Determines if the boiler is operating when the heating plant may not be required, and calculates Potential Savings and Energy Impact. {BLR}
Compare the rolling 4-hour average outdoor air temperature to the boiler lockout temperature.

Insight is triggered when Potential Savings exceeds the yearly threshold (defined by the user). This can be changed to trigger Energy Impact. Also generates PotentialSavings_DailyCUSUM ($) CTL.

  • Potential Savings is the energy cost based on the time the boiler is enabled above the desired OAT threshold, a forecast in $/year. The rule estimates only 26 weeks of boiler operation for a year (defined by the user)
  • Energy Impact is the number of daily hours boiler operating above threshold (expressed in percent of total daily hours boiler is on)

Logic

Enhanced Prioritization – Determine if boiler is operating when OAT is above lockout temperature
  • 1. Boiler plant operating above OAT lockout. Verify heating plant sequence of operation.
  • 2. Automatic control has been overridden. Revert equipment back to automatic control.

Message

The boiler has been operating while the OAT is above its lockout temperature. Ensure that boiler enable is not overridden, then verify sequence of operation.

Notes

Default values for constants: Energy Rate ($/kWh): 0.07 Threshold – PotentialSavings Yearly [$]: 100 Boiler Enable OAT Setpoint [deg]: 20 deg C / 68 deg F Voltage 3-Phase [V] {voltage}: 480 Power Factor [p.f] {pf}: 0.85 Estimated Weeks Of Boiler Operation: 26 Boiler Amperage Threshold for Running [A]: 0.5 Threshold-Weekly Energy Impact [%]: 14

Rule Template Type

  • Insight Type: Fault Detection
  • Trigger Type: Active High

Inputs

InputsUnitsDefault ValueTagsDescription
Boiler Amps [Amps] {boiler, sensor, current}Amps boiler, sensor, currentAmperage TL from Boiler
Outdoor Air Temp [deg] {sensor, outside, air, temp}°C or °F sensor, outside, air, tempOutdoor Air Temperature TL
Energy Rate [$/kWh]Amps0.07 Local utility rate
Threshold – PotentialSavings Yearly [$]Days100 Threshold to trigger potential savings Insight
Voltage 3-Phase [V]Volts480 3-Phase Line-to-Line Voltage
Power Factor [p.f] 0.85 Power Factor
Estimated Weeks Of Boiler OperationWeeks26 Estimated number of weeks Boiler will be running
Boiler Amperage Threshold for Running [A]Amps0.5 Minimum amperage from boiler before it is considered to be running.
Boiler Enable OAT Setpoint [deg]°C or °F16 Outdoor Air Temperature that the boiler should not run above
Threshold-Weekly Energy Impact [%]%14 Threshold to trigger Energy Impact

Output Calculated Trend Logs

Output CTLUnitsDescription
Boiler_EnergyImpact_Daily(%)%Daily Energy Impact of boiler operating above OAT threshold
Boiler_PotentialSavings_DailyCUSUM($)$Cumulative sum of the daily potential savings
Trigger-PotentialSavings_Yearly$Yearly potential savings