NIST APAR28 – Mode of operation changing state too frequently (Mode Changes)

Applicable Systems

  • NISTAPAR: APAR28
  • Primary: AHU, RTU, MUA, ERV

Objective/Method/Outcome

  • Objective: ndicates that the AHU mode of operation state is changing too rapidly.
  • Method: Counts the number of chenges in modes of operation per hour.
  • Outcome: An insight is generated when the number of changes in modes of operation is more than 3 times per hour.

Logic

 If (Mode changes per Hour > Max number of changes) { return true; }
NIST APAR28 – Mode of operation changing state too frequently (Mode Changes)

Inputs

  • AHU_MODE_CTL {ahu, mode} (Real Trend Log)

Parameters

ParameterExpression Block Series NumberDescriptionDefault Value (Units)
ParameterExpression Block Series NumberDescriptionDefault Value (Units)
Max number of changes allowed per hour4The amount of number of changes allowable for the unit per hour. Anything more than that time is considered a fault.12 (h)